Output Programming; Type - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
10
10.1

Output programming

Output programming is done via EBLWin. See the EBLWin dialog
box respectively.

Type

The following output types are available (see also comments below):
0. Control
1. Fire Ventilation
2. Extinguishing
3. Alarm Device
4. Routing Equipment (Fire brigade tx)
5. Control, neutral
6. Interlocking Output
Comments to the types:
0. Default. General (normal) control output
1. Used to activate fire ventilation equipment
2. Used to activate extinguishing equipment
3. Used for sounders, etc.
4. Used for fire alarm tx
5. General (normal) control output. No collective disablement and
no LED indication.
6. Output used together with a corresponding interlocking input.
See chapter "Interlocking function", page 88. Activated outputs
are shown in menu H9/C1.
70
Collectively disabled via menu H2/B4 (all control outputs). Re-enabled
via menu H2/B8.
71
Collectively disabled via menu H2/B4 (all ventilation outputs).
enabled via menu H2/B8. LED "Ventilation" is indicating activated output.
72
Collectively disabled via menu H2/B4 (all extinguishing outputs). Re-
enabled via menu H2/B8.
output.
73
Collectively disabled / re-enabled via menu H2/B9 (all alarm device
outputs). Controlled by push button "Silence alarm devices". Fault on /
disabled output is indicated by LED "Fault / Disablements Alarm devices"
blinking (fault) / continuous (disablement).
74
Disabled / re-enabled via menu H2/B10 (Fire and/or fault outputs).
Controlled via open door (if programmed so). Used together with trigger
condition Fire brigade tx. LED "Fire brigade tx" is indicating activated
output. (Fire brigade tx feedback via a programmable input can light up the
LED instead). Fault on / disabled output is indicated by LED "Fault /
Disablements Fire brigade tx" blinking (fault) / continuous (disablement).
EBL128 Planning Instructions V2.0.x
70
72
73
74
LED "Extinguishing" is indicating activated
72
71
Re-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents