Quiet Alarm; Fire Alarm Type A And Fire Alarm Type B - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
13.13
13.14
Annunciation function. Only Analog photo electric smoke detector
4301 / 4401 and Analog multi detector 4300 / 4400 can be used for
AAF. If the Analog multi detector 4300 / 4400 is used, it must be
programmed as type "Two addresses", so that only the "smoke part" of
the detector can be used for AAF.
Max. 50 AAF zones can be used.
The AAF buzzer (e.g. Sounder base 3379) has to be programmed with
the output trigger condition "AAF zone alarm".

Quiet alarm

Quiet alarm is e.g. used in conjunction with the I/O Matrix board
108
4582
, an application board for fan control and an I/O unit 3361 for
fan control.
Smoke detectors, programmed for quiet alarm, can be used e.g. for
controlling fans (stop / start depending on the type of fan).
Indications and actions:
 In the c.i.e. display:
user definable text message (alarm text) if programmed.
 LED:s "Fire" in the c.i.e. are blinking (0.4 / 0.4 sec.).
 Buzzer in the c.i.e. sounding (0.8 / 5 sec.).
 Programmable outputs for quiet alarm, e.g. 3361 outputs
controlling supply air fans and standard fans i.e. any output
with a control expression containing trigger conditions "Quiet
Alarm Zone" or "Quiet Alarm Zone Address".
Quiet alarms are non-latching, i.e. they will be automatically reset
when the alarm point / zone is no longer above alarm level.
NOTE! Quiet alarm can also be programmed for a 3361 unit "zone
line input". In such a case only non-latching detectors can be used.

Fire alarm type A and Fire alarm type B

Normally the c.i.e. relay output "R0" is used as an output for Routing
equipment (Fire brigade tx).
The output shall be programmed (via EBLWin) as type "Routing
equipment" and have the trigger condition "Fire brigade tx". The
output will then be activated for fire alarm from any alarm point or
zone line input.
If the fire alarm routing equipment has provision for transmission of
several fire alarm signals and the alarm receiver has provision for
reception of several fire alarm signals, a fire alarm type B will indicate
that only one detector is activated, which could be a nuisance alarm.
If a fire alarm type A is received, the probability of a real fire is higher
108
See "I/O Matrix board 4582", page 22.
107
EBL128 Planning Instructions V2.0.x
Quiet alarm detector ZZ/AA
and a