User Definable Text Messages Download - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
19.3

User definable text messages download

Each alarm point, zone and zone line input can have a unique user
definable alarm text programmed via EBLWin. When a fire alarm is
activated (e.g. an addressable alarm point), the presentation number
(Zone - Address) will be shown in the control unit display and in the
ext. FBP 1826 / 1828 display
All alarm texts, up to 40 alphanumeric characters each, are created and
downloaded (included in the site specific data – SSD) via EBLWin.
When a printer is available (e.g. in an Ext. FBP 1826) the alarm text
will be printed with the presentation number.
A fault message for an alarm point, zone or zone line input will also
show the alarm text.
134
This is also valid for the Ext. Presentation unit 1728 and the Alert
Annunciation units 1735 / 1736.
153
EBL128 Planning Instructions V2.0.x
134
together with its alarm text.