Programmable outputs

EBL128 has two programmable voltage outputs (S0 and S1) and one
programmable relay output (R0). 8 relay outputs expansion board
4581 can be mounted in EBL128. Input and Output expansion board
4583 with three programmable outputs (Output 0-2) can be mounted
in EBL128. See chapter "Expansion boards 458x", page 24.
On the COM loop can be connected Addressable Multipurpose I/O
unit 3361 with two programmable relay outputs (Re0 and Re1) per
unit and Addressable 2 voltage outputs unit 3364 with two
programmable voltage outputs (VO0 and VO1) per unit. Addressable
siren 3377 / 4477, Addressable sounder base 3379, Addressable
beacon 4380 and Addressable Light indicator 4383 can also be
connected on the COM loop, i.e. these units have no physical output,
only a siren, sounder, beacon, etc.
NOTE!
Units type 3377 + 3378 + 3379 + 4477 = max. 50.
Units type 4380 = max. 10.
Each output is programmed (via EBLWin), when applicable,
regarding:
Name (Normally not changed)
Type
Output signal period (continuous, pulse, delay, etc.)
Logic (NO / normally low or NC / normally high)
Supervised / Not Supervised (The EBL128 voltage outputs, the
Input and Output expansion board 4583 voltage outputs (Output
0-1) and Addressable 2 voltage outputs unit 3364.)
Control expression (with one or more trigger conditions).
If Enter arguments in dialog is selected a separate dialog box
will open for easier entering of the required data (e.g. zone,
address, etc.). SSD size indicates how big the control expression
is. It must be < 80.
Figure 11.
The EBLWin dialog boxes for the control unit
outputs.
EBL128 Planning Instructions V2.0.x