Disable Zone; Disable Zone-Address; Disable Output; Disable All Control, Ventilation, Exting Or Interlocking Outputs - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
13.15.1
13.15.2
13.15.3
13.15.4
13.15.5
13.15.6
13.15.7
shall not be selected, see chapter "System properties, Page 2", page
136.
NOTE! Enhanced Disablement is NOT valid when a time channel is
used for disablements, only when menu H2/B1-B2 are used.

Disable zone

A whole zone (all addressable alarm points within one zone, except
the manual call points) can be disabled via menu H2/B1. This menu is
also used to disable a conventional zone, i.e. a 3361 unit's zone line
input (Z) and expansion board 4580 zone line inputs.
Re-enable via menu H2/B5 or automatic re-enabling at a specified
time.

Disable zone-address

Individual alarm points can be disabled via menu H2/B2.
Re-enable via menu H2/B6 or automatic re-enabling at a specified
time.
A time channel can instead be used to disable and re-enable
automatically.

Disable output

Individual control outputs can be disabled via menu H2/B3. Disabled
output will stay in (or return to) the normal condition for the output
respectively until Re-enable via menu H2/B7.
Disable all control, ventilation, exting or interlocking
outputs
The control outputs of type "Control (general)", "Fire ventilation",
"Extinguishing system" or "Interlocking" can be collectively disabled
via menu H2/B4. Disabled outputs will stay in (or return to) the
normal condition for the output respectively until Re-enable via menu
H2/B8.

Disable / Re-enable alarm devices

The control outputs of type "Alarm device (sounder)" can be
collective disabled via menu H2/B9. Disabled outputs will stay in (or
return to) the normal condition for the output respectively until Re-
enable via menu H2/B9.

Disable / Re-enable outputs for routing equipment

The control outputs of type "Routing equipment (Fire brigade tx and
Fault tx)" can be collective disabled via menu H2/B10. Disabled
outputs will stay in (or return to) the normal condition for the output
respectively until Re-enable via menu H2/B10.

Disable / Re-enable alert annunciation function

The alert annunciation function can be disabled via menu H2/B11.
Disabled alert annunciation function will be disabled until Re-enable
via menu H2/B11.
109
EBL128 Planning Instructions V2.0.x