Logic; Not Supervised (Default); Supervised - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
8.2
8.2.1
8.2.2
26. Used for the "outside switch" (i.e. the New Zealand FB Silence
switch).
27. Pre-warning, e.g. from a High Sensitive Smoke Detector's pre-
warning output. Zone no. and Address set to the same as the
corresponding fire alarm (from the same detector).
28. A technical warning is neither an alarm nor a fault. It is activated
as long as the input is activated, which is indicated by a blinking
[i] in the display. Identified via menu H4/U6. Output with trigger
condition "Technical warning (+name)" will be activated.
29. The Addressable multipurpose I/O unit 3361 monitored input
"In0" used as zone line input (Z) for conventional detectors.

Logic

The logic has to be set (in the EBLWin dialog box "Input Properties").

Not supervised (default)

(•) Normally open (low) Normally open contact / normally low
optocoupler input (3361).
( ) Normally closed (high) Normally closed contact / normally high
optocoupler input (3361).

Supervised

Valid for the c.i.e. programmable input I0 and the Inputs and Outputs
expansion board 4583 programmable inputs (Input 0-4).
(•) Normally open (high resistance)
( ) Normally closed (low resistance)
Depending on the selected logic, Normally open (high resistance,
3K3) or Normally closed (low resistance, 680R), the function will be
according to the table on page 64.
EBL128 Planning Instructions V2.0.x
67