Units Connected To The Rs232 Interface J3 - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
6.4
The Web-server II consists of a light grey plastic cabinet
(90x25x69.5 mm), which shall be vertically mounted on the
symmetric 35 mm DIN rail inside the EBL128 c.i.e.
Web-server II has the following interfaces:
RS232 to connect the web-server to J5 in the EBL128 c.i.e.
RS232 to connect the web-server to other PC / system
RJ45 (10 BASE-T) to connect the web-server to Internet / an
intranet (LAN)
Molex 3.5 to connect the web-server to a power supply (24 V
DC, max. 65 mA), e.g. to J4 in the EBL128 c.i.e.

Units connected to the RS232 interface J3

J3 is a 9 ways female "D" connector. This interface is used only for
connection of a PC with the PC program EBLWin to an EBL128 c.i.e.
EBLWin is used for download / backup of the Site Specific Data
(SSD), new software (firmware) download, the Web-server
configuration, etc.
EBL128 Planning Instructions V2.0.x
58