Alert Annunciation - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
13.11

Alert Annunciation

In some installations the Alert Annunciation function can be used to
avoid unwanted false alarms (nuisance alarms) to the fire brigade. A
time channel can turn on/off this function.
Trained personnel are required on site to locate the fire (the room) and
take the correct measures/actions depending on if there is a fire or not.
Normally analog smoke detectors and zones with smoke detectors
only, come in question to be programmed (via EBLWin) for alert
annunciation. Heat detectors and manual call points should normally
not come in question for Alert Annunciation. A manual call point can
only activate the AA function if there are no other fire alarms
activated in the system (i.e. the second fire alarm will turn off the AA
105
function)
.
The AA function is normally turned on (enabled) during daytime
working hours only. A time channel can turn on/off (enable / disable)
the AA function. When the AA function is turned on (enabled) it is
indicated by the LED Routing equipment "Fire brigade tx delay" on
the c.i.e. front. Normally only one time channel is used for this
function but two or more channels can be used. The AA function can,
as an alternative, be continuously "on".
NOTE! The AA function can be de-activated (turned off) via menu
H2/B11 and will then stay so until turned on (normal) again via menu
H2/B11.
Figure 21. The Alert Annunciation function flow chart.
Alert Annunciation function:
Indications, print-outs, actions, etc. for an AA alarm are the same as
for a normal fire alarm except the output "Fire alarm" for routing
equipment (fire brigade tx) in the c.i.e. that will not be activated
106
directly.
104
Using an internal time channel is a VdS violation.
105
This is valid even if "Multiple alarms within same zone" is selected (via
EBLWin).
106
NOTE! Programmable outputs type "Fire brigade tx" will however be
activated if not the following is added to the control expression: AND NOT
Alert Annunciation Activated.