1.4 d: Reference Settings
• Up/Down
The frequency reference value will be saved when the Run command or the drive power is switched off. The drive will use
the frequency reference that was saved when it restarts.
Clearing the Saved Value
Depending on which function is used, it is possible to clear the saved frequency reference value by:
• Releasing the input programmed for Acceleration hold.
• Setting an Up or Down command while no Run command is active.
n
d4-10: Up/Down Frequency Reference Limit Selection
Selects how the lower frequency limit is set when using the Up/Down function.
Function on page 80
for details on the Up/Down function in combination with frequency reference limits.
No.
d4-10
Setting 0: Lower Limit is Determined by d2-02 or Analog Input
The lower frequency reference limit is determined by the higher value of either parameter d2-02 or an analog input (A1, and
A2) that is programmed for "Frequency bias".
Note:
For example, if the command to switch the external reference (H1-oo = 2) is used to switch between the Up/Down function and an analog
input as the reference source, the analog value becomes the lower reference limit when the Up/Down command is active. Change d4-10 to
1 to make the Up/Down function independent of the analog input value.
Setting 1: Lower Limit is Determined by Parameter d2-02
Only parameter d2-02 sets the lower frequency reference limit.
u

d6: Field Weakening

n
d6-01: Field Weakening Level
Sets the drive output voltage for the Field Weakening function as a percentage of the maximum output voltage. Enabled when
a multi-function input is set for Field Weakening (H1-oo = 63).
No.
d6-01
n
d6-02: Field Weakening Frequency Limit
Sets the minimum output frequency at which field weakening can be activated. Field Weakening cannot be activated for
frequencies below d6-02.
No.
d6-02
56
Power supply
OFF
ON
Forward Run / Stop
OFF
Hold Accel/Decel
Frequency reference
Output frequency
Hold
Figure 1.27 Frequency Reference Hold with Accel/Decel Hold Function
Parameter Name
Up/Down Frequency Reference Limit Selection
Parameter Name
Field Weakening Level
Parameter Name
Field Weakening Frequency Limit
ON
OFF
OFF
ON
OFF
ON
Hold
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
ON
ON
d4-01 = 1
d4-01 = 0
Refer to Settings 10 and 11: Up/Down
Setting Range
0, 1
Setting Range
0 to 100%
Setting Range
0 to 400.0 Hz
Default
0
Default
80%
Default
0.0 Hz