Setting 1: Multi-step Speed Operation Enabled
Multi-step speed inputs are still active and can override the frequency reference from the communications option even when
the NetRef command is selected.
n
F6-08: Reset Communication Parameters
Determines whether F6-oo/F7-oo communication-related parameters are reset after initialization.
No.
F6-08
Setting 0: Do Not Reset F6-oo/F7-oo Parameters after Initialization Using A1-03
Setting 1: Reset F6-oo/F7-oo Parameters after Initialization Using A1-03
Note:
F6-08 is not reset when the drive is initialized.
u

CC-Link Parameters

Parameters F6-04, F6-10, F6-11, and F6-14 set the drive to operate on a CC-Link network.
n
F6-04: bUS Error Detection Time
Sets the delay time for bUS error detection.
No.
F6-04
n
F6-10: CC-Link Node Address
Sets the node address of a CC-Link option board.
No.
F6-10
n
F6-11: CC-Link Communication Speed
Sets the communication speed for a CC-Link option card.
No.
F6-11
Setting 0: 156 kbps
Setting 1: 625 kbps
Setting 2: 2.5 Mbps
Setting 3: 5 Mbps
Setting 4: 10 Mbps
n
F6-14: bUS Error Auto Reset
Selects whether a bUS error can be automatically reset if automatic fault retry is enabled.
No.
F6-14
Setting 0: Disabled, Auto Reset Not Possible
Setting 1: Enabled, Auto Reset Possible
u

MECHATROLINK Parameters

n
F6-20: MECHATROLINK Station Address
Sets the station address when the MECHATROLINK option is installed.
Note:
All station addresses must be unique. Setting this parameter to 20 or 3F will trigger a Station Address Error (AEr) and turn on the "ERR"
light.
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
Parameter Name
Reset Communication Parameters
Parameter Name
bUS Error Detection Time
Parameter Name
CC-Link Node Address
Parameter Name
CC-Link Communication Speed
Parameter Name
bUS Error Auto Reset
1.6 F: Option Settings
Setting Range
Default
0, 1
Setting Range
0.0 to 5.0 s
Setting Range
0 to 64
Setting Range
0 to 4
Setting Range
0, 1
0
Default
2.0 s
Default
0
Default
0
Default
0
1
71