Table 8: Occupancy determination
Sequence of operation (highest to lowest priority)
Manual
Occupancy
Mode
Occupancy BI
(OCCOVRD-
(BI1‑S, BI2‑S)
MODE)
Occupied
Unoccupied
No Override
Closed
1
Open
1
Not Configured
1
Not Configured means that neither BI1 Config nor BI2 Config is set to Occupancy BI. Open and Closed refer to the
current state of the BI when configured as Occupancy.
2
True is triggered by interacting with the screen during a scheduled unoccupied period. A value of True can only occur
when the schedule is not Occupied.
3
When triggered by a BI configured for Temp Occ, the input is ignored when the schedule is Occupied, the Manual
Occupancy Mode is not No Override, or an Occupancy BI is configured.
4
Built-in occupancy sensing (PIR) or EI configured for Motion NO or Motion NC.
5
Not Set occurs when no events are scheduled through the local scheduler, or the schedule source is set to Schedule and
the Schedule is writing Not Set as the schedule.

Selecting schedule source

Scheduling (for networked models)
About this task:
The TEC3000 Thermostat Controller can operate as a stand-alone unit with an internal schedule or
scheduled with an external schedule. The OCC-CONFIG object sets the method used for scheduling.
If the OCC-CONFIG is set to External, the NET-OCC object is used to control the unit externally.
If the OCC-CONFIG is set to Schedule, the internal schedule commands the LOCAL-OCC object,
which sets the Occupancy Schedule command.
Note: If you do not have a schedule in the Schedule object and you have the OCC-CONFIG set
to Schedule, you can control the unit with the LOCAL-OCC object externally; however, we do
not recommend this method. See Table 9 for scheduling information.
Once the Occupancy Schedule command is set, the effective occupancy is determined by
settings shown in the Occupancy Determination table. See Table 8.
Occupancy
Schedule (External
or Schedule)
Temporary
(OCC‑CONFIG,
,
1
Occupancy
2
3
NET‑OCC)
NOT Occupied
1
True
2
NOT Occupied
True
3
False
Occupied
Unoccupied
Standby
Not Set
TEC3000 Series On/Off or Floating Fan Coil Thermostats Installation Guide
Motion
Sensor
4
True
False
Disabled
True
5
False
Disabled
Status indicated
Effective
Occupancy
Occupancy
Source
(EFF‑OCC)
(OCCSOURCE‑S)
Occupied-
Occ Override
Override
Unoccupied-
Override
Occupied
Occupancy BI
Unoccupied
Temp Occupancy Temp Occ
Temp Occupancy Temp Occ BI
Occupied
Occupancy
Sensor
Standby
Occupied
Occupancy
Schedule
Unoccupied
Standby
Occupied
Occupancy
Sensor
Unoccupied
Occupied
Occupancy
Schedule
35