Fault codes
(cont.)
Fault code
System character-
on the dis-
istics
play
b4
Regulates as if the
outside temperature
was 0 °C
b5
Control mode as per
delivered condition
b7
Burner blocked.
bA
Mixer M2 continues
to regulate.
bC
Control mode with-
out remote control
bd
Control mode with-
out remote control
bE
Control mode
bF
Control mode
C2
Control mode
Cd
Control mode
CE
Control mode
CF
Control mode
Cause
Measures
Internal fault
Replace the control unit.
Internal fault
Replace the control unit.
Boiler coding card
Plug in boiler coding
missing, faulty or
card or replace it, if
incorrect boiler
faulty.
coding card
Communication
Check the extension kit
fault, extension
connections and coding.
kit for mixer cir-
Start the extension kit.
cuit M2
Communication
Check connections,
fault
Vitotrol re-
cable, coding address
mote control,
"A0" and the remote
heating circuit A1
control DIP switches.
Communication
Check connections,
fault, Vitotrol re-
cable, coding address
mote control,
"A0" and the remote
heating circuit M2
control DIP switches.
Vitotrol remote
Check remote control
control incorrectly
DIP switch setting (see
programmed
page 126)
Incorrect LON
Replace the LON com-
communication
munication module.
module
Communication
Check connections and
fault, solar control
coding address "54".
unit
Communication
Check connections and
fault Vitocom 100
the Vitocom 100.
(KM BUS)
Communication
Check connections and
fault - ext. exten-
settings of coding ad-
sion
dress "2E".
Communication
Replace the LON com-
fault, LON com-
munication module.
munication mod-
ule
Troubleshooting
95