Viessmann VITODENS 343-F WS4A Installation And Service Instructions Manual page 79

Compact energy tower with a gas fired condensing boiler as compact model; natural gas and lpg version
Table of Contents

Advertisement

Code 2
(cont.)
Coding in the delivered condition
A5:5
With heating circuit
pump logic function
(economy circuit): Heat-
ing circuit pump "OFF"
if the outside tempera-
ture (AT) is 1 K higher
than the set room tem-
perature (RT
AT > RT
Parameter address
A5:...
1
2
3
4
5
6
7
to
15
Possible change
A5:0
A5:1
to
A5:15
)
set
+ 1 K
set
With heating circuit pump logic function: Heating
circuit pump "OFF", if
AT > RT
+ 5 K
set
AT > RT
+ 4 K
set
AT > RT
+ 3 K
set
AT > RT
+ 2 K
set
AT > RT
+ 1 K
set
AT > RT
set
AT > RT
- 1 K
set
AT > RT
- 9 K
set
Coding
Without heating circuit
pump logic function
With heating circuit pump
logic function: Heating
circuit pump "OFF", if
(see the following table)
79