Coding
Code 2
(cont.)
Coding in the delivered condition
65:...
Information regarding
the type of diverter
valve (not adjustable)
67:40
3. Set DHW value
6C:100
Set speed; internal cir-
culation pump with
DHW heating 100 %
6F:...
Maximum output for
DHW heating; defaulted
by the boiler coding
card
71:0
DHW circulation pump:
According to time pro-
gram: "ON" (separate
switching times are
possible for the Vitotrol
300)
72:0
DHW circulation pump:
According to time pro-
gram: "ON"
73:0
DHW circulation pump:
According to time pro-
gram: "ON "
General
76:0
Without LON communi-
cation module
74
Possible change
65:0
Without diverter valve
65:1
Diverter valve by
Viessmann
65:2
Diverter valve by Wilo
65:3
Diverter valve by Grund-
fos
67:0
Set DHW value adjusta-
to
ble from 0 to 60 °C
67:60
6C:0
Set speed adjustable
to
from 0 to 100 %
6C:100
6F:0
Max. output during DHW
to
heating adjustable from 0
6F:100
to 100 %
71:1
"OFF" during DHW heat-
ing to the first set value
71:2
"ON" during DHW heat-
ing to the first set value
72:1
"OFF" during DHW heat-
ing to the second set
value
72:2
"ON" during DHW heat-
ing to the second set
value
73:1
During the time program
to
1x/h "ON" for 5 min
73:6
up to 6x/h "ON" for 5 min
73:7
permanently "ON"
76:1
With LON communication
module; automatic recog-
nition