Viessmann VITODENS 343-F WS4A Installation And Service Instructions Manual page 77

Compact energy tower with a gas fired condensing boiler as compact model; natural gas and lpg version
Table of Contents

Advertisement

Code 2
(cont.)
Coding in the delivered condition
9C:20
Monitoring LON sub-
scribers
When there is no re-
sponse from a subscri-
ber, values defaulted by
the control unit continue
to be used for a further
20 min. Only then will a
fault message be is-
sued.
9F:8
Differential temperature
8 K; only in conjunction
with a heating circuit
with mixer
Boiler circuit, mixer circuit
A0:0
Without remote control
A3:2
Outside temperature
below 1 °C: Heating cir-
cuit pump "ON"
Outside temperature
above 3 °C: Heating cir-
cuit pump "OFF"
Note
When selecting a value
below 1 °C, there is a
risk of pipes outside the
thermal envelope of the
building being damaged
by frost. The standby
mode, in particular,
should be taken into
consideration, e.g. dur-
ing holidays.
Possible change
9C:0
No monitoring
9C:5
The time is adjustable
to
from 5 to 60 min
9C:60
9F:0
Differential temperature
to
adjustable from 0 to 40 K
9F:40
A0:1
With Vitotrol 200 (auto-
matic recognition)
A0:2
With Vitotrol 300 (auto-
matic recognition)
A3:-9
Heating circuit pump
to
"ON/OFF" (see the fol-
A3:15
lowing table)
Coding
77