Viessmann VITODENS 343-F WS4A Installation And Service Instructions Manual page 93

Compact energy tower with a gas fired condensing boiler as compact model; natural gas and lpg version
Table of Contents

Advertisement

Fault codes
(cont.)
Fault code
System character-
on the dis-
istics
play
10
Regulates as if the
outside temperature
was 0 °C
18
Regulates as if the
outside temperature
was 0 °C
20
Regulates without
flow temperature
sensor (low loss
header)
28
Regulates without
flow temperature
sensor (low loss
header)
30
Burner blocked
38
Burner blocked
40
Mixer closes.
48
Mixer closes.
50
No DHW heating
58
No DHW heating
92
Control mode
Cause
Measures
Outside tempera-
Check the outside tem-
ture sensor
perature sensor (see
shorted out
page 99).
Outside tempera-
Check the outside tem-
ture sensor lead
perature sensor (see
broken
page 99).
System flow tem-
Check the low loss
perature sensor
header sensor (see
shorted out
page 101).
System flow tem-
Check the low loss
perature sensor
header sensor (see
lead broken
page 101).
Boiler water tem-
Check the boiler water
perature sensor
temperature sensor (see
shorted out
page 101).
Boiler water tem-
Check the boiler water
perature sensor
temperature sensor (see
lead broken
page 101).
Heating circuit
Check the flow tempera-
with mixer M2
ture sensor.
flow temperature
sensor shorted
out
Heating circuit M2
Check the flow tempera-
flow temperature
ture sensor.
sensor lead bro-
ken
Cylinder tempera-
Check sensors (see
ture sensor
page 101).
shorted out
Cylinder tempera-
Check sensors (see
ture sensor lead
page 101).
broken
Solar: Collector
Check the sensor (see
temperature sen-
page 102).
sor S1 at the
Vitosolic shorted
out
Troubleshooting
93