Viessmann VITODENS 343-F WS4A Installation And Service Instructions Manual page 75

Compact energy tower with a gas fired condensing boiler as compact model; natural gas and lpg version
Table of Contents

Advertisement

Code 2
(cont.)
Coding in the delivered condition
77 :1
LON subscriber number 77 :2
79:1
Control unit is fault
manager
7b:1
Send time via LON
7F:1
Detached house
80:1
With 5 s delay for fault
message; message is
displayed if fault is pre-
sent for at least 5 s
81:1
Automatic summer/win-
ter time changeover
82:0
Operation with natural
gas
88 :0
Temperature displayed
in °Celsius
8A:175
Never adjust
90:128
Time constant for calcu-
lating the adjusted out-
side temperature
21.3 hours
Possible change
LON subscriber number,
to
adjustable from 1 to 99:
77 :99
1-4 = Compact boiler
5 = Never adjust
10 - 98 = Vitotronic 200-H
99 = Vitocom
Note
Allocate each number
only once.
79:0
Control unit is not fault
manager
7b:0
Do not send time via LON
7F:0
Apartment block
Separate adjustment of
holiday program and time
program for DHW heat-
ing, as option
80:0
Without time delay
80:2
Time delay adjustable
to
from 10 to 995; 1 step =
80:199
5 s
81:0
Manual summer/winter
time changeover
81:2
Radio clock module is
automatically detected
81:3
Accept time via LON
82:1
Operation with LPG (only
adjustable if coding ad-
dress 11:9 has been set;
see page 112)
88 :1
Temperature display in °
Fahrenheit
90:0
Fast (low values) or slow
to
(high values) matching of
90:199
the flow temperature,
subject to the set value
when the outside tem-
perature changes;
1 step = 10 min
Coding
75