Viessmann VITODENS 343-F WS4A Installation And Service Instructions Manual page 65

Compact energy tower with a gas fired condensing boiler as compact model; natural gas and lpg version
Table of Contents

Advertisement

Further details regarding the individual steps
Note
Set code "24:1" and then code "24:0" if a service is carried out before the ser-
vice display is shown; the set service parameters for hours run and interval are
then reset to 0.
Press the following keys:
1. c
The service scan is active.
2. a/b Scan service messages.
3. d
The service display will be
cleared (for a weather-
compensated control unit:
"Acknowledge: Yes",
reconfirm with d).
The red fault display con-
tinues to flash.
After a service has been carried out
1. Reset code "24:1" to "24:0".
The red fault indicator extin-
guishes.
Note
If coding address "24" is not reset,
the "Service" message reappears
after 7 days.
Commissioning, inspection, maintenance
(cont.)
Note
An acknowledged service message
can be redisplayed by pressing d
(approx. 3 s).
2. Reset the burner hours run, burner
starts and consumption, if required
Press the following keys:
c
Scanning is active.
a/b
for the selected value.
e
the selected value will be
set to "0".
a/b
for further scans.
d
Scanning is completed.
65