Code 2
(cont.)
Coding in the delivered condition
F2:8
Time limit for party
mode 8 hours or exter-
nal heating program
changeover via key
F8:-5
For the operation in re-
duced room tempera-
ture mode, the set room
temperature will be
raised (up to the tem-
perature limit set by
coding address F9) to a
value subject to the out-
side temperature, if the
outside temperature
falls below -5 °C.
Observe the setting of
coding address A3.
F9:-14
Below an outside tem-
perature of -14 °C, the
set room temperature
will be raised to the
value selected as set
room temperature, if the
system operates with
the standard room tem-
perature
FA:20
Raising the set flow
temperature for the
transition from opera-
tion with reduced tem-
perature to operation
with standard room
temperature 20 %
Fb:30
Duration for raising the
set flow temperature
(see coding address
FA): 60 min
*1
Party mode ends automatically in heating program "rw" when the system changes
over to operation with standard room temperature.
Possible change
F2:0
No time limit for party
mode
F2:1
Time limit adjustable from
*
to
1
1 to 12 hours
F2:12
F8:+10
Limit for raising the tem-
to
perature in reduced
F8:-60
mode adjustable from
+10 to -60 °C
F8:-61
Function disabled
F9:+10
Limit for raising the set
to
room temperature to the
F9:-60
value selected for stan-
dard mode adjustable
from +10 to -60 °C
FA:0
Raising the set flow tem-
to
perature for the transition
FA:50
from reduced room tem-
perature mode to stan-
dard room temperature
mode, adjustable from 0
to 50 %
Fb:0
Duration for raising the
to
set flow temperature ad-
Fb:150
justable from 0 to 150
(corresponds to 0 to 300
min)
Coding
*
1
83