Connection Of The Grounding Cable - Mitsubishi Electric MDS-E Series Instruction Manual

Table of Contents

Advertisement

MDS-E/EH Series Instruction Manual
2 Wiring and Connection

2.5.2 Connection of the Grounding Cable

(1) Connecting the protective grounding (PE) and frame ground (FG)
Each unit has a terminal or mounting hole to connect PE (
Please connect a grounding cable to the main ground of a cabinet or a machine frame at one point.
Ground each device according to the grounding conditions set forth by each country. (Typically, a Y-connection
neutral point ground is used in Europe.)
PE: Grounding to provide protection from electric shock, etc.
FG: Grounding to stabilize the operation of the devices, etc. (Suppress noise)
POINT
Do not connect the grounding cable from each unit directly to the grounding plate. Noise from other units could result in
malfunctions.
Unit
(2) Grounding cable size
Earth wire size should follow the following table.
Type
MDS-E/EH-CV Unit
MDS-E/EH-V1/V2/V3/SP/SP2 Unit
D/DH-AL (AC Reactor)
IB-1501229-F
MDS-E/EH-V1/V2/V3/SP/SP2
Servo motor
Spindle motor
Grounding
plate
Grounding cable size (Required grounding)
Larger than thickness of wire connected to TE1 (L1/L2/L3). (PE)
Larger than thickness of wire connected to TE1 (U/V/W). (PE)
(For two or three axes, the thickness of wire which the total current can be
applied to.)
2
5.5 mm
(AWG10) or more (PE)
) or FG.
MDS-E/EH-CV
D/DH-AL
Grounding plate
82