Outside Finish Installation (non-Cool Wall)—Clearances
The clearances listed below are minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance
that this fireplace and vent system be installed only in accordance with these instructions.
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
G800EC Outside Finish Clearance Requirements
Clearance:
A: Mantel Height (min.)
B: Sidewall
25" (635mm) one side only
C: Ceiling
D: Mantel Depth (max.)
E: Alcove Width
F: Alcove Depth
Notes:
C
D
E
F
Alcove
|
30
Grandview® G800EC Gas Fireplace
Dimension
10" (254mm)
Top of Fireplace Opening
Side of Fireplace Opening
36-1/2" (927mm)
Top of Fireplace Opening
12" (305mm)
Top of Fireplace Opening
84" (2134mm)
Wall to Wall (Minimum)
36" (914mm)
Front to Back Wall (Maximum)
0"
No Hearth Required
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fireplace and vent
system be installed only in accordance with these instructions.
Measured From:
Minimum Vent Clearances
to Combustibles
Horizontal Top
Horizontal Side
Horizontal Bottom
Vertical Vent
WARNING
Fire hazard is an extreme risk
2" (51mm)
1-1/2 " (38mm)
1-1/2" (38mm)
1-1/2" (38mm)