For the return temperature object, enter the following:
Configure the "RS-485 B" port (M-Bus Master) using the above requirements
•
Click on the RS-485 B Configuration tab.
Select M-Bus Master from the protocol dropdown menu.
•
Enter the Baud Rate to match that of the RS-485 to M-Bus converter.
•
•
Create Service Objects to read the desired data.
o
Create one service object to monitor the volume flow.
o
Create a service object to monitor the flow temperature.
•
Enter "4" into the Database Addr field.
•
Select 32-bit Signed from the Data Type dropdown
menu.
•
Enter "1" into the Multiplier field.
•
Select Celsius (62) from the Units dropdown menu.
•
Click Create.
•
Select Analog Input from the Type selection group.
•
Enter "Return Temp" into the Object Name field.
•
Enter "2" into the Instance field.
•
Enter "8" into the Database Addr field.
•
Select 32-bit Signed from the Data Type dropdown
menu.
•
Enter "1" into the Multiplier field.
Select Celsius (62) from the Units dropdown menu.
•
Click Create.
•
Enter the address of the heat meter into the Dest Address
•
field.
Enter "0" into the Database Addr field.
•
•
Select 32-bit Signed from the Data Type dropdown
menu.
Enter "1" into the Multiplier field.
•
•
Uncheck Manually Enter Bytes in the Data Information
Block (DIB) group and select No Data / Auto Detect from
the Data Field dropdown.
•
Uncheck Manually Enter Bytes in the Value Information
Block (VIB) group and select Volume Flow 1000 [ml/s]
from the Unit and Multiplier dropdown.
•
Uncheck the "Send Data" function code check box (this is
a monitor-only parameter, so there will be no need to write
to it)
Click Create.
•
Enter the address of the heat meter into the Dest Address
•
field.
Enter "4" into the Database Addr field.
•
Select 32-bit Signed from the Data Type dropdown
•
menu.
Enter "1" into the Multiplier field.
•
67