For the return temperature object, enter the following:
Configure the "RS-485 B" port (M-Bus Master) using the above requirements
Click on the RS-485 B Configuration tab.
Select M-Bus Master from the protocol dropdown menu.
Enter the Baud Rate to match that of the RS-485 to M-Bus converter.
Create Service Objects to read the desired data.
o
Create one service object to monitor the volume flow.
o
Create a service object to monitor the flow temperature.
Enter "4" into the Database Addr field.
Select 32-bit Signed from the Data Type dropdown
menu.
Enter "1" into the Multiplier field.
Select Celsius (62) from the Units dropdown menu.
Click Create.
Select Analog Input from the Type selection group.
Enter "Return Temp" into the Object Name field.
Enter "2" into the Instance field.
Enter "8" into the Database Addr field.
Select 32-bit Signed from the Data Type dropdown
menu.
Enter "1" into the Multiplier field.
Select Celsius (62) from the Units dropdown menu.
Click Create.
Enter the address of the heat meter into the Dest Address
field.
Enter "0" into the Database Addr field.
Select 32-bit Signed from the Data Type dropdown
menu.
Enter "1" into the Multiplier field.
Uncheck Manually Enter Bytes in the Data Information
Block (DIB) group and select No Data / Auto Detect from
the Data Field dropdown.
Uncheck Manually Enter Bytes in the Value Information
Block (VIB) group and select Volume Flow 1000 [ml/s]
from the Unit and Multiplier dropdown.
Uncheck the "Send Data" function code check box (this is
a monitor-only parameter, so there will be no need to write
to it)
Click Create.
Enter the address of the heat meter into the Dest Address
field.
Enter "4" into the Database Addr field.
Select 32-bit Signed from the Data Type dropdown
menu.
Enter "1" into the Multiplier field.
67