Create one service object to monitor the controlling temperature.
o
Create a final service object to control the setpoint values.
Finishing Up
•
Download the configuration to the gateway (see section 8.1 for more
information on downloading a configuration to a device).
•
Connect the gateway to the water heater and the BAS.
•
Uncheck the "write" function code check box (these are
monitor-only parameters, so there will be no need to write
to them)
•
Enter "5.12" for the Multiplier since these values are
scaled by 512 on the water heater and we would like to
preserve 2 decimal places.
•
Click Create.
•
Enter "0" into the Block Num field.
•
Enter "5" into the Start Param field.
•
Enter "1" into the Num Params field.
Enter "4" into the Database Addr field.
•
•
Uncheck the "write" function code check box (these are
monitor-only parameters, so there will be no need to write
to them)
Enter "5.12" for the Multiplier.
•
Click Create.
•
Enter "0" into the Block Num field.
•
Enter "6" into the Start Param field.
•
•
Enter "2" into the Num Params field.
•
Enter "100" into the Database Addr field.
•
Check both the "read" and "write" function code check
boxes.
•
Enter "5.12" for the Multiplier.
•
Click Create.