Create one service object to monitor the controlling temperature.
o
Create a final service object to control the setpoint values.
Finishing Up
Download the configuration to the gateway (see section 8.1 for more
information on downloading a configuration to a device).
Connect the gateway to the water heater and the BAS.
Uncheck the "write" function code check box (these are
monitor-only parameters, so there will be no need to write
to them)
Enter "5.12" for the Multiplier since these values are
scaled by 512 on the water heater and we would like to
preserve 2 decimal places.
Click Create.
Enter "0" into the Block Num field.
Enter "5" into the Start Param field.
Enter "1" into the Num Params field.
Enter "4" into the Database Addr field.
Uncheck the "write" function code check box (these are
monitor-only parameters, so there will be no need to write
to them)
Enter "5.12" for the Multiplier.
Click Create.
Enter "0" into the Block Num field.
Enter "6" into the Start Param field.
Enter "2" into the Num Params field.
Enter "100" into the Database Addr field.
Check both the "read" and "write" function code check
boxes.
Enter "5.12" for the Multiplier.
Click Create.