Open the configuration utility and select the XLTR-1000 (see section 8.1 for
more information on selecting a device).
Click on the RS-485 A Configuration tab.
Select BACnet MS/TP Server from the protocol dropdown menu.
Enter the Baud Rate settings to match that of the BAS.
Enter the Address at which the gateway will reside on the network.
Enter a Device Name, device Instance Number, and the Max Master for
the gateway.
Create BACnet objects to map the data from the gateway's database to the
BAS. The monitor object data will start at database address 0 and the
command object data will start at database address 100.
o
Create objects for temperature monitoring points
For the first object, enter the following:
Repeat these steps for the other two temperature points, increasing
the Instance by 1, and Database Addr by 2 each time.
o
Create objects for the operating setpoint
Enter the following:
Configure the "RS-485 B" port (PDNP Master) using the above requirements
Click on the RS-485 B Configuration tab.
Select AO Smith PDNP Master from the protocol dropdown menu.
Create Service Objects to read and write the desired data.
o
Create one service object to monitor the temperatures.
Select Analog Input from the Type selection group.
Enter "Inlet Temp" into the Object Name field.
Enter "0" into the Instance field.
Enter "0" into the Database Addr field.
Select 16-bit Unsigned from the Data Type dropdown
menu.
Enter "0.01" into the Multiplier field.
Select Celsius (62) from the Units dropdown menu.
Click Create.
Select Analog Output from the Type selection group.
Enter "Op Setpoint" into the Object Name field.
Enter "0" into the Instance field.
Enter "100" into the Database Addr field.
Select 16-bit Unsigned from the Data Type dropdown
menu.
Enter "0.01" into the Multiplier field.
Select Celsius (62) from the Units dropdown menu.
Click Create.
Enter the address of the boiler into the Dest Address field.
Enter "0" into the Start Param field.
Enter "3" into the Num Params field.
Enter "0" into the Database Addr field.
Uncheck the "write" function code check box (these are
monitor-only parameters, so there will be no need to write
to them)