ICC
•
Open the configuration utility and select the XLTR-1000 (see section 8.1 for
more information on selecting a device).
•
Click on the RS-485 A Configuration tab.
•
Select BACnet MS/TP Server from the protocol dropdown menu.
•
Enter the Baud Rate settings to match that of the BAS.
•
Enter the Address at which the gateway will reside on the network.
Enter a Device Name, device Instance Number, and the Max Master for
•
the gateway.
•
Create BACnet objects to map the data from the gateway's database to the
BAS. The monitor object data will start at database address 0 and the
command object data will start at database address 100.
o
Create objects for temperature monitoring points
For the first object, enter the following:
Repeat these steps for the other two temperature points, increasing
the Instance by 1, and Database Addr by 2 each time.
o
Create objects for the operating setpoint
Enter the following:
Configure the "RS-485 B" port (PDNP Master) using the above requirements
•
Click on the RS-485 B Configuration tab.
•
Select AO Smith PDNP Master from the protocol dropdown menu.
•
Create Service Objects to read and write the desired data.
o
Create one service object to monitor the temperatures.
•
Select Analog Input from the Type selection group.
Enter "Inlet Temp" into the Object Name field.
•
Enter "0" into the Instance field.
•
Enter "0" into the Database Addr field.
•
Select 16-bit Unsigned from the Data Type dropdown
•
menu.
Enter "0.01" into the Multiplier field.
•
Select Celsius (62) from the Units dropdown menu.
•
•
Click Create.
•
Select Analog Output from the Type selection group.
•
Enter "Op Setpoint" into the Object Name field.
•
Enter "0" into the Instance field.
•
Enter "100" into the Database Addr field.
•
Select 16-bit Unsigned from the Data Type dropdown
menu.
•
Enter "0.01" into the Multiplier field.
•
Select Celsius (62) from the Units dropdown menu.
•
Click Create.
•
Enter the address of the boiler into the Dest Address field.
•
Enter "0" into the Start Param field.
•
Enter "3" into the Num Params field.
•
Enter "0" into the Database Addr field.
•
Uncheck the "write" function code check box (these are
monitor-only parameters, so there will be no need to write
to them)
36