Open the configuration utility and select the XLTR-1000 (see section 8.1 for
more information on selecting a device).
Click on the RS-485 A Configuration tab.
Select Modbus RTU Master from the protocol dropdown menu.
Enter the Baud Rate and Parity settings to match that of the servo motor.
Create Service Objects to write to the desired registers:
o
We can create one service object to command both the X and Y
positions.
Configure the "RS-485 B" port (DMX-512 Slave) using the above requirements
Click on the RS-485 B Configuration tab.
Select DMX-512 Slave from the protocol dropdown menu.
Enter "49" for the Address, as this is the next free DMX channel.
Enter "0" for the Database Start Address.
Enter "4" for the Num Channels.
Finishing Up
Download the configuration to the gateway (see section 8.1 for more
information on downloading a configuration to a device).
Connect the gateway to the servo motor and the DMX controller.
Where are the control values?
Database
Servo Parameter
Address
0
X (Coarse Adjustment)
1
X (Fine Adjustment)
2
Y (Coarse Adjustment)
3
Y (Fine Adjustment)
Note that the database endianness is assumed to be big endian in this example.
Select Holding Register from the Type selection.
Enter the address of the servo motor into the Dest
Address field.
Enter "100" into the Start Reg field.
Enter "2" into the Num Regs field.
Enter "0" into the Database Addr field.
Click Create.
DMX
Channel
49
Register 100 (Upper Byte)
50
Register 100 (Lower Byte)
51
Register 101 (Upper Byte)
52
Register 101 (Lower Byte)
62
Modbus Register