ICC

9.3 BACnet MS/TP

The gateway supports both BACnet MS/TP client and server drivers on both of its
RS-485 ports. Both client and server act as an MS/TP master on the network,
meaning they are actively involved in token management.

9.3.1 Protocol Implementation Conformance Statement

BACnet Protocol
Date:
Vendor Name:
Product Name:
Product Model Number:
Applications Software Version: V2.400
Firmware Revision:
BACnet Protocol Revision:
Product Description:
The XLTR-1000 is a multiprotocol RS-485 to RS-485 gateway. This
product supports native BACnet, connecting directly to the MS/TP LAN
using baud rates of 4800, 9600, 19200, 38400, 57600, 76800, and
115200. The device can be configured as a BACnet Client or as a
BACnet Server.
BACnet Standard Device Profile (Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
BACnet Interoperability Building Blocks Supported (Annex K):
Data Sharing – ReadProperty-A (DS-RP-A)
Data Sharing – ReadProperty-B (DS-RP-B)
Data Sharing – ReadPropertyMultiple-B (DS-RPM-B)
Data Sharing – WriteProperty-A (DS-WP-A)
Data Sharing – WriteProperty-B (DS-WP-B)
Data Sharing – WritePropertyMultiple-B (DS-WPM-B)
Device Management – Dynamic Device Binding-A (DM-DDB-A)
Device Management – Dynamic Device Binding-B (DM-DDB-B)
Device Management – Dynamic Object Binding-B (DM-DOB-B)
Device Management – DeviceCommunicationControl-B (DM-DCC-B)
Device Management – ReinitializeDevice-B (DM-RD-B)
August 22, 2008
ICC, Inc.
Millennium Series Multiprotocol RS485 Gateway
XLTR-1000
V2.400
2