ICC
Bit 3 – Audio Triggers on Caution
Bit 4 – Audio Triggers on Warning
Bit 5 – Audio Triggers on Alarm
Bit 6 – Audio Triggers on Trouble
Bit 7 – Audio Triggers on Auxiliary
Status
This parameter provides status information generated by the gateway containing
the communication status to the monitor module and validity of concentration
values. This is a bit-wise parameter with the following bit mapping:
Bit 0 – S1 Valid
Bit 1 – S2 Valid
Bit 2 – S3 Valid
Bit 3 – S4 Valid
Bit 4 – S5 Valid
Bit 5 – S6 Valid
Bit 6 – S7 Valid
Bit 7 – S8 Valid
Bit 8 – Com Error (1=gateway not receiving transmissions from monitor)
Note that bits #0..#7 of the status parameter will be "1" when the monitor is
configured to sample the indicated sensor, and is sending the associated
concentration values and gas type to the gateway. This occurs only when the
monitor is showing the home screen on its display (i.e. if the user navigates away
from the monitor's home screen, these bits will become "0").
Sx Gas Number
This parameter, one for each of 8 samples, is the numerical encoding of the gas
type currently being sampled for that point. Refer to Table 7 for a definition of the
gas number encoding. Note that the gas number value will not be updated in the
gateway if the corresponding sensor status bit is not valid (e.g. if the home
screen is currently not being display on the monitor).
Gas
Gas Type
Number
0
UNDEF
1
R-11
2
R-12
3
R-13
4
R-13B1
5
R-14
Table 7: Chillgard Gas Number Definitions
Gas
Number
51
52
Ethylene Oxide
53
Cyclopentane
54
55
Trichloroethylene
Dowtherm J
56
Diethyl Benzene
Gas Type
Number
R-1132a
Ethanol
125
Gas
Gas Type
102
M-Xylene
103
P-Xylene
104
N-Hexane
105
N-Pentane
106
Hex-Fluor-Pro
107
Tetra-Fl-Eth