ICC
Database
Address
0
8
16
24
32
40
48
56
64
I/O State
This parameter is the I/O state of the monitor module overall. It may have the
following values:
0 – Warmup
1 – Ready
2 – Trouble
3 – Cal / Setup
Alarm Data
This parameter provides alarm information for the monitor module overall. This is
a bit-wise parameter with the following bit mapping:
Bit 6 – Audio On
Bit 7 – Alarm Latched
Audio Preferences
This parameter provides audio and latching preferences that are currently
configured for the monitor module. This is a bit-wise parameter with the following
bit mapping:
Bit 0 – Latching Caution Relay
Bit 1 – Latching Warning Relay
Bit 2 – Latching Alarm Relay
Table 6: Chillgard Database Mapping
+0
I/O State
Alarm Data
S1 Gas
Number
Concentration
S2 Gas
Number
Concentration
S3 Gas
Number
Concentration
S4 Gas
Number
Concentration
S5 Gas
Number
Concentration
S6 Gas
Number
Concentration
S7 Gas
Number
Concentration
S8 Gas
Number
Concentration
+2
Preferences
S1 Gas
S1 Alarm
S2 Gas
S2 Alarm
S3 Gas
S3 Alarm
S4 Gas
S4 Alarm
S5 Gas
S5 Alarm
S6 Gas
S6 Alarm
S7 Gas
S7 Alarm
S8 Gas
S8 Alarm
124
+4
Audio
Status
Reserved
State
Reserved
State
Reserved
State
Reserved
State
Reserved
State
Reserved
State
Reserved
State
Reserved
State
+6