Create objects for the first light's control channels
For the red control, enter the following:
o
For the green, blue, and dimmer control channels, repeat the
previous steps, changing the Object Name and incrementing the
Instance and Database Addr fields each time.
o
For the other light, repeat the previous steps, changing the Object
Name to use a "2" instead of a "1" and continue incrementing the
Instance and Database Addr fields each time. When complete, the
configuration should contain 8 consecutive analog input objects
starting at instance 0 mapped to 8 consecutive bytes starting at
address 0 in the database.
Configure the "RS-485 B" port (DMX-512 Master) using the above requirements
Click on the RS-485 B Configuration tab.
•
Select DMX-512 Master from the protocol dropdown menu.
•
Enter "0" for the Database Start Address.
•
Enter "8" for the Num Channels.
•
Finishing Up
•
Download the configuration to the gateway (see section 8.1 for more
information on downloading a configuration to a device).
•
Connect the gateway to the two lights and the BAS.
•
Configure one of the light's DMX addresses to 1 and the other to 5
•
Select Analog Output from the Type selection group.
•
Enter "Red 1" into the Object Name field.
•
Enter "0" into the Instance field.
•
Enter "0" into the Database Addr field.
•
Select 8-bit Unsigned from the Data Type dropdown
menu.
•
Enter "1" into the Multiplier field.
•
Select No Units (95) from the Units dropdown menu.
•
Click Create.