7 Electrical Installation
Model
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4477
-, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4568
-, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4605
-, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4720
-, +1
+3
*1
For IP20 protection, use wires that are in the range of applicable gauges.
*2
Remove insulation from the ends of wires to expose the length of wire shown.
*3
For wire gauges more than AWG 8, tighten to a tightening torque of 4.1 N∙m to 4.5 N∙m (36 in∙lb to 40 in∙lb).
*4
Terminals - and +1 have two screws. The Recommended Gauge is the wire gauge for one terminal.
*5
A junction terminal is necessary to connect a braking resistor unit (LKEB-series) to terminals B1 and B2.

Main Circuit Terminal Block Wiring Procedure

DANGER
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized drive. Before servicing,
disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal capacitor
stays charged after the drive is de-energized. The charge indicator LED extinguishes when the DC bus voltage decreases below 50
Vdc. When all indicators are OFF, remove the covers before measuring for dangerous voltages to make sure that the drive is safe. If
you do work on the drive when it is energized, it will cause serious injury or death from electrical shock. The drive has internal
capacitors that stay charged after you de-energize the drive.
40
Applicable Gauge
Recommended
(IP20 Applicable
Gauge
Gauge
*1
AWG, kcmil
AWG, kcmil
2/0 - 300 × 4P
250 × 4P
(250 - 300 × 4P)
2/0 - 300 × 4P
4/0 × 4P
(250 - 300 × 4P)
3/0 - 400 × 4P
4/0 × 4P
(300 - 400 × 4P)
2 - 4/0
3/0 × 4P
(4/0 × 4P)
1/0 - 300
1/0
(-)
2/0 - 300 × 4P
250 × 4P
(250 - 300 × 4P)
2/0 - 300 × 4P
4/0 × 4P
(250 - 300 × 4P)
3/0 - 400 × 4P
300 × 4P
(300 - 400 × 4P)
2 - 4/0 × 4P
3/0 × 4P
(4/0 × 4P)
2/0 - 300
2/0
(-)
2/0 - 300 × 4P
300 × 4P
(250 - 300 × 4P)
2/0 - 300 × 4P
300 × 4P
(250 - 300 × 4P)
3/0 - 400 × 4P
400 × 4P
(300 - 400 × 4P)
2 - 4/0 × 4P
4/0 × 4P
(4/0 × 4P)
2/0 - 300
2/0
(-)
2/0 - 300 × 4P
300 × 4P
(250 - 300 × 4P)
2/0 - 300 × 4P
300 × 4P
(250 - 300 × 4P)
3/0 - 400 × 4P
400 × 4P
(300 - 400 × 4P)
2 - 4/0 × 4P
4/0 × 4P
(4/0 × 4P)
2/0 - 300
2/0
(-)
Wire Stripping
*2
Length
)
Size
mm
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
YASKAWA TOEPC71061737B GA800 Drive Installation & Primary Operation
Terminal Screw
Tightening Torque
N∙m (in∙lb)
Shape
Hex self-locking nut
Hex self-locking nut
Hex self-locking nut
Hex self-locking nut
Hex bolt (slotted)
(283 - 354)
Hex self-locking nut
Hex self-locking nut
Hex self-locking nut
Hex self-locking nut
Hex bolt (slotted)
(283 - 354)
Hex self-locking nut
Hex self-locking nut
Hex self-locking nut
Hex self-locking nut
Hex bolt (slotted)
(283 - 354)
Hex self-locking nut
Hex self-locking nut
Hex self-locking nut
Hex self-locking nut
Hex bolt (slotted)
(283 - 354)
35
(310)
35
(310)
35
(310)
35
(310)
32 - 40
35
(310)
35
(310)
35
(310)
35
(310)
32 - 40
35
(310)
35
(310)
35
(310)
35
(310)
32 - 40
35
(310)
35
(310)
35
(310)
35
(310)
32 - 40