Led Status Ring - YASKAWA GA800 Series Installation & Primary Operation

Ac drive for industrial applications
Hide thumbs Also See for GA800 Series:
Table of Contents

Advertisement

9

LED Status Ring

The LED Status Ring on the drive cover shows the drive operating status.
A - ALM/ERR
B - Ready
LED
A
ALM/ERR
Flashing Quickly
B
Ready
C
RUN
Flashing Quickly
*1
Refer to
Figure 9.1
for the difference between "flashing" and "flashing quickly".
YASKAWA TOEPC71061737B GA800 Drive Installation & Primary Operation
Status
The drive detects a fault.
Illuminated
The drive detects:
• An alarm
• An oPE parameter setting error
*1
Flashing
• An Auto-Tuning error
Note:
The LED will illuminate to identify a fault if the drive detects a fault and an alarm at the same time.
OFF
There are no drive faults or alarms.
The drive is operating or is prepared for operation.
Illuminated
*1
The drive is in STo [Safe Torque OFF] condition.
Flashing
The voltage of the main circuit power supply dropped, and only the external 24 V power supply provides the power to the
*1
drive.
• The drive detects a fault.
• There is no fault and the drive received a Run command, but the drive cannot operate. For example, in Programming
OFF
Mode or when
The drive is in regular operation.
Illuminated
• The drive is decelerating to stop.
*1
• The drive received a Run command with a frequency reference of 0 Hz, but the drive is not set for zero speed control.
Flashing
• The drive received a DC Injection Braking command.
• The drive received a Run command from the MFDI terminals and is switching to REMOTE Mode while the drive is in
LOCAL Mode.
• The drive received a Run command from the MFDI terminals when the drive is not in Drive Mode.
• The drive received a Fast Stop command.
• The safety function shuts off the drive output.
*1
• The user pushed
• The drive is energized with an active Run command and b1-17 = 0 [Run Command at Power Up = Disregard Existing
RUN Command].
• The drive is set to coast-to-stop with timer (b1-03 = 3 [Stopping Method Selection = Coast to Stop with Timer]), and the
Run command is disabled then enabled during the Run wait time.
The motor is stopped.
OFF
C - RUN
Description
is flashing.
on the keypad while the drive is operating in REMOTE Mode.
9 LED Status Ring
51

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga80u seriesGa800

Table of Contents