10 Drive Start-Up Procedure
■
External Power Supply Input Terminals
Refer to
Table 10.4
for a list of the functions of the external power supply input terminals.
Type
External Power Supply Input
Terminals
■
Serial Communication Terminals
Refer to
Table 10.5
for a list of serial communication terminals and functions.
Type
Modbus Communication
◆
Control Circuit Terminal Configuration
The control circuit terminals are in the positions shown in
A - Terminal block (TB5)
B - Terminal block (TB2-3)
C - Terminal block (TB2-2)
D - Terminal block (TB2-1)
The tightening torque for the terminal screws is shown on the reverse side or the lower front side of the front cover.
58
Table 10.4 External Power Supply Input Terminals
Terminal
Name (Default)
PS
External 24 V power supply input
AC
External 24 V power supply ground
Table 10.5 Serial Communication Terminals
Terminal
Terminal Name
Communication
MEMOBUS/Modbus communications
D+
input/output (+)
Use an RS-485 cable to connect the drive.
Communication
D-
output (-)
0 V
AC
Signal ground
Figure 10.1 Control Circuit Terminal Arrangement
Supplies backup power to the drive control circuit, keypad, and option board.
21.6 VDC to 26.4 VDC, 700 mA
0 V
Function (Signal Level)
Note:
Set DIP switch S2 to ON to enable the
termination resistor in the last drive in a
MEMOBUS/Modbus network.
Figure
10.1.
E - Terminal block (TB1)
F - Terminal block (TB3)
G - Terminal block (TB4)
YASKAWA TOEPC71061737B GA800 Drive Installation & Primary Operation
Function
• RS-485
• MEMOBUS/Modbus communication protocol
• Maximum 115.2 kbps