9 Operation at Use of the Display
9.4 Parameterization
Table 9-7
Current - Deadband
Power - Deadband
Power factor - Deadband
Frequency - Deadband
1)
After enabling the parameter changes, any currently active Modbus TCP connections will be closed. The
Modbus TCP client must later re-open these connections.
Table 9-8
Bus protocol
Device address
Baud rate
Parity
Access rights
Communication supervision time
Baud rate
Parity
Additional inter-character timeout
Maximum 0x/1x register gap
Maximum 3x/4x register gap
294
Ethernet Communication Settings (cont.)
Serial Communication Settings – Modbus RTU and Modbus RTU Master Bus Protocols
Parameter
Bus Protocol Modbus RTU (Slave)
Bus Protocol Modbus RTU Master
5 %
1 % to 5 % in increments of 1 %
5 %
1 % to 5 % in increments of 1 %
5 %
2% to 5 % in increments of 1 %
0,05
0.02 %
0.05 %
Default Setting
Modbus RTU
None
Modbus RTU
Modbus Master
1
1 to 247
19 200 bit/s
For the selection, see Chapter 15
Even
For the selection, see Chapter 15
Full
Full
Read only
600 * 100 ms
0 s = none
100 ms to 6 553 400 ms
19 200 bit/s
For the selection, see Chapter 15
even
For the selection, see Chapter 15
1 ms
0 ms to 100 ms
40
0 to 200
10
Setting Range
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018