8 Operation at Use of a PC
8.3 Configuration of the Device
8.3.3.1.3
Binary Outputs G1/G2 and G3/G2
Default Settings and Setting Ranges of the Binary Outputs G1/G2 and G3/G2
Table 8-4
Source type
Source Type Indication
Indication
Source inverted
Operating mode
Output time for pulse operating mode
(setting only possible if operating
modes Pulse and Pulse with retrig-
ger)
Source Type Energy Counter
Energy counter
Energy increase per pulse
Output time for pulse operating mode
146
Settings of Binary Outputs G1/G2 and G3/G2
Parameter
Default Setting
Indication
Indication
Energy counter
-none-
Acc. to list box
(see chapter 15)
no
no
yes
Persistent
Persistent
Persistent with fail safe
Pulse
Pulse with retrigger
20 (* 10 ms)
50 ms to 3 600 000 ms
-none-
Acc. to list box
(see chapter 15)
1.0 Wh
0.1 Wh/VAh/varh to 1 000 000 Wh/VAh/
varh
20 (* 10 ms)
50 ms to 3 600 000 ms
Setting Range
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018