8.3.7.4.3
Mapping – Indications
At Indications, the indications are defined which are read by a selected Modbus slave device.
Default Settings and Settings of the Modbus Slave Device 1
Table 8-27
Parameter
Name
Register type
Data format on bus
(see also Table 8-28.)
Register number
Bit offset
(only relevant for register types
Input register or Holding register)
Table 8-28
Data Format
on Bus
1 Bit
1 Bit in UInt32
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Settings for assignment of the indications of the Modbus slave device 1
Indication x Slv 1
(x = 1 to 6)
-none-
1 Bit
1
0
Data format on Bus
Description
1 bit (for all register types; addi-
tionall select Bit offset for Input
register and Holding register)
1 bit in 2 successive Input regis-
ters or Holding registers which
have to be read together.
Default Setting
Max. 31 characters
-none-
Coil status registers
Input status registers
Input registers
Holding registers
For -none-, the assignment is ignored
and the corresponding indication cannot
be selected for other functions.
1 Bit
1 Bit in UInt32
1 to 65 535
0 to 15 (for Data format 1 Bit)
0 to 31 (for Data format 1 Bit in UInt32)
Setting
Range
recognition
0 = of
none
1 = on
0 = of
none
1 = on
8 Operation at Use of a PC
8.3 Configuration of the Device
Setting Range
Invalid
Used by (example)
SICAM P50 7KG775,
SENTRON 3WL/3VL,
SIPROTEC4
SENTRON PAC3x00
203