Siemens SICAM Q100 Device Manual page 168

Power monitoring device and class a power quality recorder
Hide thumbs Also See for SICAM Q100:
Table of Contents

Advertisement

8 Operation at Use of a PC
8.3 Configuration of the Device
8.3.6.2 Trigger Management
Default Settings and Setting Ranges
Table 8-13
Parameter
Trigger active
Tolerance unit
Lower threshold
Upper threshold
Hysteresis
Detection mode
Trigger active
Tolerance unit
Lower threshold
Upper threshold
Hysteresis
Trigger active
Trigger source
Trigger value
168
Trigger Management
Default Setting
no
Percentage
90.00 % of the
nominal/declared
supply voltage
110.00 % of the
nominal/declared
supply voltage
2.00 % of the nominal/
declared supply
voltage
1)
ph-N
no
Percentage
90.00 %
of nominal current In
110.00 %
of nominal current In
2.00 %
of nominal current In
Configuration binary trigger
no
Binary Input 1
OFF
Voltage trigger limits
no
yes
Percentage
Numerical
0.00 % to 99.99 % of the nominal/declared supply
voltage
0.0 V to 1 000 000.0 V
100.0 % to 10 000.0 % of the nominal/declared supply
voltage
0.0 V to 1 000 000.0 V
0.0 % to 50.0 % of the nominal/declared supply
voltage
ph-N
ph-ph
Current trigger limits
no
yes
Percentage
Numerical
0.00 % to 99.99 % of of nominal current In
0.0 A to 1 000 000.0 A
100.0 % to 10 000.0 % of of nominal current In
0.0 A to 1 000 000 A
0.0 % to 50.0 % of of nominal current In
no
yes
Indication 1 from Remote
Indication 2 from Remote
Binary Input 1
Binary Input 2
ON
OFF
Waveform capture setting
Setting Range
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018