Siemens SICAM Q100 Device Manual page 174

Power monitoring device and class a power quality recorder
Hide thumbs Also See for SICAM Q100:
Table of Contents

Advertisement

8 Operation at Use of a PC
8.3 Configuration of the Device
Recording with the Trend Recorder
The recording of data points (voltage values with a time stamp) that have exceeded/fallen below the parame-
terized tolerance value (fault) and the associated creation of a PQDIF file is determined by 2 trigger criteria:
Creation of a PQDIF file after the parameterized Maximum recording interval (for example, 24 h) has
been reached if within this interval no 1024 data points have been generated yet.
Creating a PQDIF file without considering the parameterized Maximum recording interval, if the voltage
has exceeded/fallen below the tolerance range 1024 times and therefore 1024 data points have been gen-
erated.
Start time
Clock time
Recording time
Data points
PQDIF file
recording
Figure 8-47
NOTE
A data point is created when the voltage exceeds or falls below the parameterized tolerance value. The data
point represents this voltage value in the PQDIF file.
174
0:00
04:00
06:50
0
1024 / 0
Recording
all 1024 data points
Trend Recorder, Function When the 24 h Interval Is Set
08:00
12:00
14:15
1024 / 0
Recording
all 1024 data points
16:00
20:00
18:45
1024 / 0
120 / 0
Recording
Recording all
120 data points
1024 data points
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
24:00

Advertisement

Table of Contents
loading

This manual is also suitable for:

7kg95 series

Table of Contents