SECTION 5 – TECHNICAL DATA
Excessive flow will cause damage to the
cooler. Do not exceed max. cooler flow.
Special care should be taken when mul-
tiple chillers are fed by a single pump.

Voltage Limitations

The following voltage limitations are absolute and
operation beyond these limitations may cause serious
damage to the compressor.
44

TABLE 4 - VOLTAGE LIMITATIONS

UNIT POWER
200-3-60
208-3-60
230-3-60
380-3-60
460-3-60
575-3-60
FORM 201.26-NM1
ISSUE DATE: 1/19/2018
MIN.
MAX.
180
220
187
229
200
254
342
402
414
508
520
635
JOHNSON CONTROLS