SECTION 7 – UNIT CONTROLS
T O T A L
N U M B E R
C O M P R E S S O R S
The TOTAL NUMBER OF COMPRESSORS is the
total quantity of compressors in the chiller, and deter-
mines the stages of cooling available. Dual system
units may have 4 or 6 compressors.
This MUST be programmed correctly to
assure proper chiller operation.
N U M B E R
O F
P E R
S Y S T E M
Does not apply to a YCWL chiller.
S Y S
X
T R I P
U N I T
T R I P
= X . X
136
O F
=
6
F A N S
= X
V O L T S
= X . X
V O L T S
V O L T S
V O L T S
Depending on the option, the trip voltage for a
specific system or unit high current trip can be
programmed. It also calibrates the current read-
out under the OPER DATA key. The approximate
programmed value is calculated using the following
formulas:

System Trip Volts

For individual system high current trip programming
on chillers:
• Add the sum of the compressor and fan RLA's in
the system
• Multiply the sum by 1.25
• Divide by 225A
• The resulting voltage is the value that should be
programmed
For example, if fan and compressor RLA's total 100A:
5V x 100A
x
1.25 =
225A
The programmed value will be 2.8V. A similar calcula-
tion and programming will be necessary for the other
system in a 2-system chiller.
FORM 201.26-NM1
ISSUE DATE: 1/19/2018
625VA
= 2.8V
225A