Option 10 - Condenser Fan Control Mode; Option 11 - Manual Override Mode; Option 12 - Current Feedback Options Installed; Option 13 - Power Fail Restart - York YCWL0056SE Installation Operation & Maintenance

Water-cooled liquid chillers
Table of Contents

Advertisement

FORM 201.26-NM1
ISSUE DATE: 1/19/2018
or
L E A D / L A G
M A N U A L
S Y S
SYS 2 selected as lead compressor.
or
L E A D / L A G
A U T O M A T I C
Lead/lag between systems may be selected to help
equalize average run hours between systems on chillers
with 2 refrigerant systems. Auto lead/lag allows auto-
matic lead/lag of the two systems based on an average
run hours of the compressors in each system. A new
lead/lag assignment is made whenever all compressors
shut down. The microprocessor will then assign the
"lead" to the system with the shortest average run time.
Option 10 – Condenser Fan Control Mode
F A N
C O N T R O L
D I S C H A R G E
Does not apply to a YCWL chiller.
F A N
C O N T R O L
A M B I E N T
&
Does not apply to a YCWL chiller.
Option 11 – Manual Override Mode
M A N U A L
O V E R R I D E
D I S A B L E D
This option allows overriding of the Daily Schedule
that is programmed. MANUAL OVERRIDE MODE –
DISABLED indicates that override mode has no effect.
or
M A N U A L
O V E R R I D E
E N A B L E D
Manual Override Mode is enabled. This is a service
function and when enabled, will allow the unit to start
when shut down on the Daily Schedule. It will auto-
matically be disabled after 30 minutes.
JOHNSON CONTROLS
C O N T R O L
2
L E A D
C O N T R O L
P R E S S U R E
D S C H
P R E S S
M O D E
M O D E
Option 12 – Current Feedback Options
Installed
C U R R E N T
N O N E
This mode should be selected when the panel is not
equipped with current sensing capability.
or
C U R R E N T
O N E
P E R
This mode should be selected when an optional 2ACE
Module is installed to allow combined current moni-
toring of all systems by sensing current on the incom-
ing line.
or
C U R R E N T
F E E D B A C K
O N E
P E R
This mode should be selected when an optional 2ACE
module is installed to allow individual current moni-
toring of each system. SYS 1 input is to J7 of the I/O.
SYS 2 input is to J8 of the I/O.
Option 13 – Power Fail Restart
P O W E R
F A I L
A U T O M A T I C
Chiller auto restarts after a power failure.
P O W E R
F A I L
M A N U A L
After a power failure, the UNIT switch must be tog-
gled before restart at the unit is allowed. NORMALLY
MANUAL RESTART should NOT BE SELECTED.
Option 14 – Soft Start Enable/Disable
S O F T
D I S A B L E D
SOFT START "DISABLED" MUST be selected on all
chillers. This message may not be viewable on non-
European chillers.
SECTION 7 – UNIT CONTROLS
F E E D B A C K
F E E D B A C K
U N I T
S Y S T E M
R E S T A R T
R E S T A R T
S T A R T
141