FORM 201.26-NM1
ISSUE DATE: 1/19/2018

ACCEPTABLE PRINTERS

The following printer can be used. Printers must be
equipped with an RS-232 serial interface.

Okidata OKIPOS 441 Printer

• Dimensions:
6.9 inches wide x 9.64 inches deep x 5.98 inches
high
• Paper: 3.0 inches wide
• Type: Dot Matrix Impact
• Purchase: 800-OKIDATA
Spare printer Ribbon Okidata 52119001 Black
The control center provides the required formatting
control codes for the printers above when the printer
is selected on the PRINTER screen in the instructions
below. These codes are transmitted through the serial
interface to the printer to provide a proper print format.
Different printers require different formatting control
codes. Other printers might provide proper operation
when connected to the control center. However, the
print format may not be correct or as desired.
Proceed with caution, and use the following guidelines
if an unlisted printer is selected:
1. All printers must be capable of RS-232 serial
communications.
2. The primary differences between printers involve
the formatting control codes required by the print-
er, which are sent from the control center to the
printer. For example, Weigh -Tronix printers re-
quire a control code to select 40-column width.
This same code is interpreted by the Okidata
printer as an instruction to print wide characters.
In some instances, a printer will ignore a code it
cannot interpret.
3. The control center requires a busy signal from
the printer when the printer receive buffer is full,
which causes the control center to momentarily
terminate the data transmission until the printer
can accept more data. The busy signal polarity
must be asserted low when busy.
JOHNSON CONTROLS

OPTIONAL PRINTER INSTALLATION

PRINTER CONNECTIONS

Connect the printers to the control center microboard
as follows. Only one printer can be connected at a time.

TABLE 24 - OKIDATA OKIPOS 441

MICROBOARD
PRINTER
TB1-3
PIN 3
TB1-2
PIN 20
TB1-5
PIN 7
Cabinet

Required Hardware:

Cable

• #18 AWG stranded 50 ft maximum length.

Connectors

Microboard
• None. Strip 1/4 of an inch insulation from wire
and insert into screw terminal block.
Printers
• Okidata: 25 pin plug DB-25P or equivalent; Shell
DB-C2-J9 or equivalent.

PRINTER SETUP

The printer must be configured as follows. Refer to the
manual provided by the printer manufacturer.
Okidata OKIPOS 441 Printer
1. With the printer power turned off, remove the two
screws, which hold the RS-232 Interface Module.
2. Pull the RS-232 Interface Module out of the print-
er.
3. Set the DIP switch SW2-2 to OFF to select 19200
BPS. Do not change any other switch settings.
4. Reinstall the RS-232 Interface Module and two
mounting screws.
5. Load paper and install the printer ribbon into the
printer.
6. Connect the printer cable to the printer and the
microboard.
FUNCTION
TX (Data to Printer)
DSR (Busy Signal
from Printer)
Ground
Shield