Event
Description
(alphabetical)
Wrong
SIMOCODE pro parameters are
password
protected by a password. An
attempt has been made to
change the parameters without
entering the password.
Phase
The limit value for phase
unbalance
unbalance has been exceeded.
Phase unbalance can cause an
overload. Possible causes:
Phase failure
Fault in the motor windings.
Feedback
The current flow in the motor
(FB) OFF
feeder has been interrupted
without the motor feeder being
turned off.
Feedback
Current is flowing in the motor
(FB) ON
feeder without the motor feeder
being switched on
Test Position
Current is flowing in the motor
Feedback
feeder although the motor feeder
(TPF)
is in the test position (TPF).
Memory
The parameters of the memory
module read
module were read into
in
SIMOCODE.
Memory
The memory module was cleared
module
and is now back in as-delivered
cleared
state.
Memory
The reparameterization was
module
accepted in the memory module.
programmed
Memory
The memory module is
module write-
completely write-protected.
protected
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Troubleshooting
Please use the correct
password for changing the
parameters. If you do not
know the password, new
parameters can only be
entered after the factory
settings have been
restored. For a description
of how to restore the
factory settings, see
Chapter Restoring factory
settings (Page 285).
Check the motor feeder
and the motor.
The main circuit has
been interrupted (fuse,
circuit breaker, main
switch).
The motor contactor or
contactor control is
defective
Contactor contacts
have been manually
activated
Contactor has not
been switched on via
SIMOCODE
The main circuit is not
interrupted in test
operation.
Deactivate write protection
of the memory module.
Commissioning, service, troubleshooting
13.4 Troubleshooting
Acknowledgment /
Contactor
fault rectification
control
Reset
Tripped
Reset
Tripped
Clear the fault;
Tripped
reset
Reset
Tripped
Error
No.
1)
25
11
10
17
297