Siemens SIMOCODE pro C System Manual page 200

Industrial controls. motor management and control devices
Table of Contents

Advertisement

Mounting, wiring, connecting, system interfaces, configuration guidelines
12.2 Wiring, connecting
Assignment of the removable terminals, SIMOCODE pro S basic units
The following table shows the assignment of the removable terminals of the
SIMOCODE pro S basic unit:
Table 12- 6
Assignment of the removable terminals, SIMOCODE pro S basic unit
Terminal
Assignment
Upper terminals
IN+
24 V DC only for IN1 to IN4
A1
Supply voltage terminal 1
A2
Supply voltage terminal 2
A
PROFIBUS DP terminal A
B
PROFIBUS DP terminal B
SPE
System shielding
1)
IN1
Digital input IN1
IN2
Digital input IN2
IN3
Digital input IN3
Lower terminals
T1
Thermistor connection 1 (binary PTC)
T2
Thermistor connection 2 (binary PTC)
IN4
Digital input IN4
13
Common potential for relay outputs 1
and 2
14
Relay output OUT1
24
Relay output OUT2
1)
Note
Connect SIMOCODE pro via terminal SPE with the maximum possible cross-section and
with as short a cable as possible to the functional ground of the control cabinet, e.g. to the
grounded mounting plate of the control cabinet.