Commissioning, service, troubleshooting
13.4 Troubleshooting
Event
Description
(alphabetical)
Trip level
The power factor cos phi has
cos phi <
undershot the trip level. Possible
cause: The motor is being
operated without a load.
Trip level I <
The maximum current has
undershot
undershot the trip level.
Trip level I >
The maximum current has
overshot
overshot the trip level.
Trip level P <
The active power of the motor
undershot
has undershot the trip level.
Trip level P >
The active power of the motor
overshot
has overshot the trip level.
Trip level U <
The voltage in the motor feeder
undershot
has undershot the trip level.
Possible causes:
Undervoltage in the network
Fuse has tripped
Trip level
The measured value at the
0/4 - 20 mA <
analog input has undershot the
undershot
trip level.
Trip level
The measured value at the
0/4 - 20 mA >
analog input has overshot the trip
overshot
level.
Operational
An "Operational Protection
Protection Off
Off (OPO)" signal is pending. A
(OPO)
switched-on motor feeder has
been switched off. The feeder
cannot be switched on while the
OPO signal is active.
Motor
The configured limit value for
operating
motor operating hours monitoring
hours >
has been exceeded.
Stalled rotor
The maximum motor current has
exceeded the threshold for
stalled rotor protection. Possible
cause: The motor is blocked.
292
Troubleshooting
Please check the
application that is being
driven by the motor.
Please check the
application that is being
driven by the motor.
Please check the
application that is being
driven by the motor.
Please check the
application that is being
driven by the motor.
Please check the
application that is being
driven by the motor.
Check the motor feeder.
Check the measuring
station.
Check the measuring
station.
Please adopt the
maintenance measures
intended for the feeder.
Please check the
application that is being
driven by the motor.
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Acknowledgment /
Contactor
fault rectification
control
Tripped
Tripped
Tripped
Tripped
Tripped
Tripped
Tripped
Tripped
Reset
Tripped; for
positioners
QE1 or QE2
switched on
until end
position is
reached -
depending
upon
configuration
Reset
Tripped
Error
No.
1)
44
41
40
43
42
45
47
46
19
48