Siemens SIMOCODE pro C System Manual page 295

Industrial controls. motor management and control devices
Table of Contents

Advertisement

Event
Description
(alphabetical)
Initialization
The initialization module is
module write-
completely or partially write-
protected,
protected.
parameter
Reparameterization of
changes not
SIMOCODE pro is denied
allowed
because the initialization module
is write-protected.
Initialization
Reparameterization has been
module -
rejected because the initialization
identification
module is write-protected.
data write-
protected
Initialization
The parameters of the
module read
initialization module were read
in
into SIMOCODE.
Initialization
The reparameterization was
module
accepted in the initialization
programmed
module.
Initialization
The initialization module has
module
been cleared and is now back in
cleared
the as-delivered condition.
Internal
Internal ground-fault monitoring
ground fault
has responded. An impermissibly
high residual current is flowing.
No start
The permissible number of starts
permitted
in the monitoring timeframe has
been attained. The next start
should not be carried out until the
interlocking time has expired.
Module fault
At least 1 SIMOCODE pro
module is not ready for use.
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Troubleshooting
Deactivate write protection
of the initialization module
Select a
parameterization with
identical addressing
and I&M data
Deactivate the partial
write protection of the
initialization module
Please check the motor
connection cable for
damage.
Connecting cable
defective or incorrectly
connected
Module defective.
Replace the module.
See Chapter
Replacing
SIMOCODE pro
components
(Page 279).
Commissioning, service, troubleshooting
13.4 Troubleshooting
Acknowledgment /
Contactor
fault rectification
control
Reset
Tripped
Reset
Tripped
Clear the fault;
Tripped
reset
Error
No.
1)
28
1
295