Siemens SIMOCODE pro C System Manual page 197

Industrial controls. motor management and control devices
Table of Contents

Advertisement

Figure 12-13 Removable terminals for SIMOCODE pro V PN / pro V EIP basic units, expansion
Cables
The conductor cross sections are the same for all devices. The following table shows
conductor cross sections, stripped lengths, and tightening torques of the cables for the
removable terminals:
Table 12- 3
Conductor cross sections, stripped lengths, and tightening torques of the cables for the basic units
SIMOCODE pro C and pro V
Removable terminals
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Mounting, wiring, connecting, system interfaces, configuration guidelines
modules and decoupling module
Screwdriver
PZ2 / Ø 5 to 6 mm
Stripped lengths
Solid
Finely stranded
with / without end
sleeve
Tightening torque
TORQUE:
7 to 10.3 lb.in
0.8 to 1.2 Nm
Conductor cross section
2x 0.5 to 2.5 mm
/ 1x 0.5 to 4 mm
2
2x AWG 20 to 14 / 1x AWG 20 to 12
2x 0.5 to 1.5 mm
/ 1x 0.5 to 2.5 mm
2
2x AWG 20 to 16 / 1x AWG 20 to 14
12.2 Wiring, connecting
2
2
197