Siemens SIMOCODE pro C System Manual page 202

Industrial controls. motor management and control devices
Table of Contents

Advertisement

Mounting, wiring, connecting, system interfaces, configuration guidelines
12.2 Wiring, connecting
Pin assignment for SIMOCODE pro V PN / EIP basic units
The following table shows the pin assignment of the removable terminals:
Table 12- 8
Pin assignments of the removable terminals of the basic unit
Terminal
Assignment
Upper terminals
1
Common potential for relay outputs 1
and 2
2
Relay output OUT1
3
Relay output OUT2
4
Digital input IN3
5
Digital input IN4
T2
Thermistor connection (binary PTC)
6
Relay output OUT3
7
Relay output OUT3
8
24 V DC only for IN1 to IN4
9
Digital input IN1
10
Digital input IN2
T1
Thermistor connection (binary PTC)
Lower terminals
A1
Supply voltage terminal 1
A2
Supply voltage terminal 2
PORT 1
PROFINET connection 1
PORT 2
PROFINET connection 2
SPE
System shielding
1)
1)
Note
Connect SIMOCODE pro via terminal SPE with the maximum possible cross-section and
with as short a cable as possible to the functional ground of the control cabinet, e.g. to the
grounded mounting plate of the control cabinet.