Ptx10003 Clearance Requirements For Airflow And Hardware Maintenance; Prepare For The Installation - Juniper PTX10003-160C Quick Start Manual

Hide thumbs Also See for PTX10003-160C:
Table of Contents

Advertisement

PTX10003-80C and PTX10003-160C Quick Start Guide
Update your installation base at

PTX10003 Clearance Requirements for Airflow and Hardware Maintenance

When planning the site for a PTX10003 installation, you must allow sufficient clearance around the installed chassis (see
Figure 1: Clearance Requirements for Airflow and Hardware Maintenance for the PTX10003
24 in. (61 cm)
Clearance required
for maintenance
Ports
19.00 in.
(48.26 cm)
Follow these guidelines:
For the cooling system to function properly, the airflow around the chassis must be unrestricted. See PTX10003 Cooling System
Description and Airflow for more information about the airflow through the chassis.
If you are mounting a PTX10003 in a rack with other equipment, ensure that the exhaust from other equipment does not blow
into the intake vents of the chassis.
You must leave at least 24 in. (61 cm) both in front of and behind the PTX10003 for service personnel to remove and install
hardware components.

Prepare for the Installation

To install the PTX10003, you'll need either a mechanical lift or two persons to lift it into place. An additional person is needed to
secure the router to the rack.
You'll also need to have the following items available (none are provided):
ESD wrist strap with cable
Screwdriver appropriate for the rack-mounting screws
Management host, such as a PC laptop, with a serial port
(Optional) Grounding cable kit with bracket, lug, and three nuts with integrated washers.
Grounding cable—The grounding cable must be 4 AWG (8.4 mm²), minimum 90° C wire, or as permitted by the local code.
NOTE:
The grounding cable requires a Panduit LCD6-14BH-L or equivalent grounding lug. For DC installations, the
grounding lug is provided.
Two #10-32 screws and washers.
Screwdriver appropriate for the #10-32 screws.
2
https://www.juniper.net/customers/csc/management/updateinstallbase.jsp
32.43 in. (82.38 cm)
31 in. (78.74 cm)
24 in. (61 cm)
Clearance required
for maintenance
FRUs
17.28 in.
(43.90 cm)
.
Figure
Copyright © 2018, Juniper Networks, Inc.
1).