PTX10003-80C and PTX10003-160C Quick Start Guide
the weight before attempting to install the PTX10003. See Removing the AC/HVDC Power Supply from the PTX10003
and Removing the PTX10003 Fan Modules. For overhead installation—for example, if you are installing the PTX10003
above 60 in. (152.4 cm) from the floor—we recommend that you use a mechanical lift.
CAUTION:
If you are mounting multiple units in the rack, mount the heaviest unit at the bottom and mount the others
from bottom to top in order of decreasing weight. The PTX10003-160C weighs approximately 110 lb (50 kg) fully
loaded and the PTX10003-80C weighs approximately 88 lb (40 kg) fully loaded.
Wrap and fasten one end of the ESD wrist strap around your bare wrist, and connect the other end of the strap to the ESD
1.
point on the device.
Decide whether to place the field-replaceable unit end or the port end of the PTX10003 at the front of the rack. Position the
2.
PTX10003 in such a manner that the
Using a Phillips screwdriver, remove the screw on each side of the chassis that holds the mounting rails to the chassis. (see
3.
Figure 2
and
Figure
3).
Slide the mounting rail out of the mounting blades.
4.
Figure 2: Removing the Slide Rail Screw (PTX10003-160C)
Figure 3: Removing the Slide Rail Screw (PTX10003-80C)
Perform one of the following steps:
5.
Use a mechanical lift to position the PTX10003 in the rack so that the front brackets on the front mounting rails are aligned
with the rack holes.
4
label on the handle is next to the hot aisle.
AIR OUT
Copyright © 2018, Juniper Networks, Inc.