Basic Operation
5-2 V/f Control
Setting the V/f Patterns (n09 to n15)
Set the V/f pattern so that the motor output torque is adjusted to the required load
torque.
The 3G3JV incorporates an automatic torque boost function. Therefore, a maximum of
150% torque can be output at 3 Hz without changing the default settings. Check the
system in trial operation and leave the default settings as they are if no torque charac-
teristic changes are required.
Maximum Frequency (FMAX)
n09
Setting
50.0 to 400 (Hz)
range
n10
Maximum Voltage (VMAX)
Setting
1 to 255 (V)
range
Maximum Voltage Frequency (FA)
n11
Setting
0.2 to 400 (Hz)
range
n12
Middle Output Frequency (FB)
Setting
0.1 to 399 (Hz)
range
Middle Output Frequency Voltage (VC)
n13
Setting
1 to 255 (V)
range
Minimum Output Frequency (FMIN)
n14
Setting
0.1 to 10.0 (Hz)
range
Minimum Output Frequency Voltage (VMIN) Changes during
n15
Setting
1 to 50 (V)
range
5-4
Unit of
0.1 Hz
setting
(see note)
Unit of
1 V
setting
Unit of
0.1 Hz
setting
(see note)
Unit of
0.1 Hz
setting
(see note)
Unit of
1 V
setting
Unit of
0.1 Hz
setting
Unit of
1 V
setting
Chapter 5
Changes during
No
operation
Default setting
60.0
Changes during
No
operation
Default settings 200
Changes during
No
operation
Default setting
60.0
Changes during
No
operation
Default setting
1.5
Changes during
No
operation
Default setting
12
Changes during
No
operation
Default setting
1.5
No
operation
Default setting
12